ZW8-12
☆ introduce 

ZW8-12 Outdoor high voltage vacuum circuit breaker



1.Applying conditions:

Ambient temperature;-30----+40

Altitude:≤1000m;(Not including special requirement

Wind speed: ≤34m/s

 Ambient pollutionIII

Max daily temperature difference:25

Service environmentno frequent violent vibration

2. Overall drawing

Overall drawing(drawing 1)


1. Rings     2.Insulating sleeving   3. Tank cover   4. Sealing element   5. Lifting rings   6.Tank

7. Dehydrating breather   8. Opening &Closing indicator   9. Operating mechanism   10. Nameplate

 

 

 

 

 

 

 

3. Technical specification(Table2)

No.

Item

Unit

Data

1

Rated voltage

kV

12

2

Rated power frequency withstand voltage/1min

Dry

kV

42

Wet

34

3

Rated lighting impulse withstand voltage

kV

75

4

Rated frequency

Hz

50

5

Rated current

A

630

6

Rated short circuit breaking current

kA

12.5

16

20

7

Rated short circuit making current

kA

31.5

40

50

8

Rated short time withstand current(4s)

kA

12.5

16

20

9

Rated withstand current(peak)

kA

31.5

40

50

10

Rated duration of short circuit

s

4

11

Rated operating sequence


O0.3sCO180sCO

12

Opening time

ms

≤100

13

Rated short circuit breaking times

Times

30

14

Breaking current of 2 out-phase points grounding   fault 

KA

17.4

15

Arc duration

ms

≤15

16

Mechanical life

Times

10000

4. Mechanical propertytable 3

No.

Item

Unit

Data

1

Clearance between open contacts

mm

11 ± 1

2

Over-travel of contact

3±0.5

3

Bounce time of contact closed

ms

≤ 2

4

Simultaneity of 3 phase contact opened&closed

≤ 2

5

Contact force

N

1600

6

Average opening speed   

m/s

1.2±0.4

7

Average closing speed

0.65±0.15

8

Opening time

ms

30≤t≤70

9

Closing time

35≤t≤60

10

Wearing for contract permitted

mm

3

11

 Resistance for   main circuit 

μΩ

≤200

5.Secondary connection diagram




Electrical protection connection diagram of circuit breakerDC)

RemarkCurrent transformer is connected with terminal 200/5 before delivery. If user want to use terminal 400/5 or 630/5,please connect JX-31 to JX-32 or JX-33 and connect JX-34 to JX-35 or JX-36.